NUWAY COOPERATIVE,SHERBURN MN - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

NUWAY COOPERATIVE 
P.O. BOX 399,COUNTY ROAD 13 SO. 
SHERBURN MN 56171 
 
FOR FURTHER INFORMATION, CONTACT DAN SCHLEY, PLANT MANAGER, (507)764-6541. 
 
RISK MANAGEMENT PLAN-EXECUTIVE SUMMARY 
 
1.THE FACILITY POLICY 
 THE OWNERS, MANAGEMENT, AND EMPLOYEES OF NUWAY COOPERATIVE, SHERBURN, ARE COMMITTED TO THE PREVENTION OF ANY ACCIDENTAL RELEASES OF ANHYDROUS AMMONIA. IF AN ACCIDENTAL RELEASE SHOULD OCCUR, THE FACILITY IS PREPARED TO WORK WITH THE LOCAL FIRE COMPANY, OR OTHER AUTHORITIES,TO MITIGATE ANY RELEASE AND MINIMIZE THE IMPACT OF THE RELEASE TO PEOPLE AND THE ENVIRONMENT. 
 
2.FACILITY INFORMATION 
  THE PRIMARY ACTIVITY AT THE FACILITY IS THE STORAGE AND BLENDING OF FERTILIZERS FOR SALE TO FARMERS. 
 
  ANHYDROUS AMMONIA IS RECEIVED, STORED AND DISTRIBUTED FOR DIRECT APPLICATION. ANHYDROUS AMMONIA IS USED FOR CROP PRODUCTION NUTRIENTS. 
 
  THE MAXIMUM QUANTITY OF AMMONIA STORED WOULD BE 240,000 POUNDS IN OUR TWO 12,000 GALLON STORAGE TANKS AND OUR NURSE TANKS. THE MAXIMUM QUANTITY HANDLED W 
OULD BE THE UNLOADING OF A TANK TRUCK HOLDING 40,000 POUNDS. 
 
3. THE WORST-CASE RELEASE SCENARIO AND THE ALTERNATIVE RELEASE SCENARIO. 
 
A.  THE WORST-CASE RELEASE SCENARIO FOR ANHYDROUS AMMONIA WOULD E THE RELEASE OF THE TOTAL CONTENTS OF A STORAGE TANK RELEASED AS A GAS OVER TEN MINUTES. THE MAXIMUM QUANTITY RELEASED WOULD BE 55,000 POUNDS, WHICH REPRESENTS THE VOLUME OF A STORAGE TANK AT 85 PERCENT CAPACITY AS LIMITED BY DESIGN STANDARDS. THE DISTANCE TO THE ENDPOINT (POINT OF DISPERSION TO 200 PPM) IS .84 MILES. 
 
B. THE ALTERNATIVE RELEASE SCENARIO FOR ANHYDROUS AMMONIA BASED ON THE HAZARD REVIEW IS A 2 MINUTE RELEASE FROM A BREAK IN A 3 INCH PIPE.  THE DISTANCE TO THE ENDPOINT IS .78. 
 
4. THE ACCIDENTAL RELEASE PREVENTION PROGRAM 
 
  THE FACILITY HAS IMPLEMENTED THE PROVISIONS OF "SAFETY REQUIREMENTS FOR THE STORAGE AND HANDLING OF ANHYDROUS AMMONIA, K-61.1", PUBLISHED BY THE AMERICAN NATIONAL STANDARDS INSTITUTE, INC. AND THE STANDARDS OF THE U.S. OCCUPATIONAL SAFETY AND HEALTH AD 
MINISTRATION (OSHA), 29 CFR 1910.111, "STORAGE AND HANDLING OF ANHYDROUS AMMONIA".  IN ADDITION, MINNESOTA DEPT. OF AG RULES. 
 
5.THE FIVE-YEAR ACCIDENT HISTORY.                                               
                                                                                                                                                                A.THERE HAVE BEEN NO ACCIDENTAL RELEASES OF ANHYDROUS AMMONIA IN THE PAST FIVE YEARS THAT: 
   HAVE CAUSED ANY DEATHS, INJURIES, OR SIGNIFICANT PROPERTY DAMAGE AT THE FACILITY;NOR TO OUR KNOWLEDGE, HAVE RESULTED IN OFFSITE DEATHS, INJURIES, EVACUATIONS, SHELTERING IN PLACE, PROPERTY DAMAGE OR ENVIRONMENTAL DAMAGE. 
 
6. THE EMERGENCY RESPONSE PROGRAM. 
 
  THE FACILITY HAS:                                                                                                                                    
 
A.  A WRITTEN EMERGENCY ACTION PLAN, IN ACCORDANCE WITH OSHA STANDARD, 29 CFR 1910.38 
 
B.  PROVIDED STATE AND LOCAL AUTHORITIE 
S THE EMERGENCY PLANNING 
AND COMMUNITY RIGHT-TO-KNOW INFORMATION AS REQUIRED UNDER SARA TITLE III (EPCRA). 
 
C.  COORIDINATED WITH LOCAL EMERGENCY RESPONDERS. 
 
7.  PLANNED CHANGES TO IMPROVE SAFETY 
 
  SAFETY IMPROVEMENT IS AN ON-GOING PROCESS AT THE FACILITY.  PERIODIC EVALUATIONS ARE PERFORMED TO ASSESS THE MAINTENANCE OF SAFE CONDITIONS. THERE ARE NO ADDITIONAL SPECIFIC ANHYDROUS AMMONIA SAFETY RECCOMENDATIONS FOR IMPLEMENTATION AT THIS TIME.
Click to return to beginning