ACCIDENTAL RELEASE PREVENTION PROGRAM 
EXECUTIVE SUMMARY 
 
The McGregor Company 
Oakesdale Retail Facility 
Oakesdale, Washington  
 
 
1.    Facility Accidental Release Policy  
 
The owners, management, and employees of The McGregor Company along with the crew of the Oakesdale facility located at Garfield Highway Oakesdale, Washington 99158 are committed to the prevention of any accidental release of  anhydrous ammonia.  If an accidental release should occur,  the McGregor Company and the Oakesdale retail facility are prepared to work with the local fire department, or any other authorities to mitigate any release and minimize the impact of the release to people and the environment. 
 
NOTE: See planned changes to improve safety. 
 
2.    Facility Information 
 
o    The primary activity at the facility is the storage, and handling of anhydrous ammonia. 
 
o    Anhydrous ammonia is received, stored, and distributed as an agricultural grade fertilizer to local farmers. 
 
o    Anhydrous ammonia is received by truck or 
rail car, and stored in one above ground tank(s)  .The maximum amount of anhydrous ammonia handled is 130,000 lbs. 
 
 
 
3.    The Worst-Case Release Scenario and Alternative Release Scenario 
 
a.    Anhydrous Ammonia Worst-Case and Alternative Release Scenarios    
The worst-case release scenario involves the failure of the largest storage tank when filled to 85% capacity as limited by regulations. The scenario at this facility would release 130,000 pounds of anhydrous ammonia. The distance to the endpoint (the point of dispersion to 200ppm) is 1.12. This figure comes from TFI's DEGADIS model. 
 
The alternative release scenario, is based on the most likely potential incident that might occur at this facility. We used the scenario that a 2" transfer hose would break and release 11,908 pounds of anhydrous ammonia for two minutes.  The distance to the endpoint (point of dispersion to 200 ppm) is 0.56 miles. This figure come from TFI's DEGADIS model. 
 
 
 
 
4.  Accidental Release Prevention Program 
 
An 
hydrous Ammonia: The Facility has implemented the provisions of the "Safety Requirements for Storage and Handling of Anhydrous Ammonia, ANSI K 61.1,  
"Published by the American National Standards Institute, Inc, the standards of the U.S. Occupational Safety and Health Administration (OSHA), 29 CFR 1910.111, "Storage and Handling of Anhydrous Ammonia." And TFI's "Guidelines for Safe Storage and Handling of Ammonia" 
 
 
 
5.  Five-year Accident History 
   a.    There have been no accidental releases or near misses of anhydrous ammonia in the past five years that: 
 
o    Have caused any deaths, injuries, or significant property damage at the facility; nor 
 
o    Have resulted in off-site deaths, injuries, evacuations, sheltering in place, property damage, or environmental damage. 
 
6.  The Emergency Action Policy  
The facility's emergency action policy was written in accordance with the following 
Regulations: 
 
o    OSHA 29 CFR 1910.38; 
   o    OSHA 29 CFR 1910.120; 
 
7. Planned Changes to Improve Safety and Facili 
ty Accidental Release Policy. 
   The McGregor Company and its 33 retail fertilizer facilities located in Washington, Idaho and Oregon have an outstanding record on safety and environmental issues. We have an excellent safety and maintenance program and have won several regional, State and national environmental respect awards. Safety and environmental improvements are an ongoing process for the McGregor Company and all of its retail fertilizer facilities. 
 
NOTE: 
   As a result of the RMP program the McGregor Company will be developing new plans and policies to protect the people who work at our facilities, our neighbors and the environment. At this time The McGregor Company would ask for an exemption on filing an Emergency Response Plan.  We ask that the McGregor Company be exempt until Dec. 31 1999. We apply for this exemption because of information received from EPA 10th District 112 r coordinator. During this time we will develop a complete written Emergency Response plan for all of The 
McGregor Company retail fertilizer facilities.  The written plan would be complete by Sept. 1 1999.  Next we will present the plan to all of the employees at our retail facilities.  Awareness and training would start right away.  Training would be scheduled around fall fertilizer season.  All training to be completed by Dec. 31, 1999, As soon as possible or by the end of Jan. 2000 we will submit an updated RMP.