Alliant Foodservice, Detroit - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

                        ALLIANT FOODSERVICE, INC. 
 
                         RISK MANAGEMENT PROGRAM 
                                                    EXECUTIVE SUMMARY 
 
1.  General accidental release and prevention policy of Alliant Foodservice. 
 
In this frozen food distribution center we utilize anhydrous ammonia as a refrigerant.  Anhydrous 
ammonia is considered hazardous by the Environmental Protection Agency. The same properties 
that make ammonia a valuable refrigerant also makes it necessary to observe certain safety 
precautions during it's use to prevent exposure to our workers, the surrounding community and 
the environment.   
It is our policy at Alliant Foodservice to implement the requirements of the Risk Management 
Program by managing and operating this facility in full compliance with all applicable federal and 
state regulations that we are governed by. The objective is to minimize the risk of an accidental 
release of hazardous materials. Safety depends directly on our p 
roper handling of ammonia. Our 
plant personnel have been trained on the equipment operating procedures and the various safety 
devices that are incorporated in our facility to prevent the possibility of accidental releases. 
 
2.  Stationary source and regulated substance handled. 
 
Alliant Foodservice, 27000 Wick Road, Taylor, Michigan operates a refrigeration system utilizing 
anhydrous ammonia as the primary refrigerant. Mechanical refrigeration is a thermodynamic 
process where the refrigerant, ammonia, is used as a heat exchanging fluid to maintain a desired 
temperature in an enclosed environment. The refrigeration cycle consists of evaporation, 
compression, condensation and expansion. Evaporation and condensation are designed to alter the 
quantity of energy associated with the refrigerant. Compression and expansion are designed to 
change the availability of the associated energy. The refrigeration cycle is a closed loop process. 
The ammonia cycle utilizes fluid temperature, pressure an 
d latent heat of vaporization for cooling. 
The refrigeration system uses this phenomenon to remove heat from a desired space, and then to 
discard that heat through condensation, to an area where it is of no consequence. 
 
The Alliant Foodservice facility uses ammonia refrigeration to maintain storage room 
temperatures for various types of fresh and frozen food distributed to their customers. The 
refrigeration system contains the following equipment: Four screw compressors, one evaporative 
condensers, one high pressure receiver, two recirculators, one liquid transfer vessel, one 
thermosyphon tank, thirty cooler/freezer evaporators, a floor warming heat exchanger and a 
system purger. The refrigeration system contains 25,000 pounds of aggregate ammonia. 
 
There are approximately 230 employees at this facility which includes hourly and salary personnel.  
This distribution facility receives and prepares shipment of frozen and refrigerated food products 
via tractor trailers approximately 24 ho 
urs a day, six days a week.   
 
 
 
The potential hazards that could lead to an accidental release of the ammonia include, but are not 
limited to, equipment failure, damage to piping, damage to equipment, human error, etc. 
 
Although ammonia is a colorless, tasteless liquid, it's dominant characteristic is it's pungent, 
distinct odor.  Persons exposed to ammonia will not voluntarily stay in areas of even small 
concentrations, although these levels would not normally result in any health risks. Risks from 
accidental exposure to ammonia in a vapor state are irritations to the eyes, nose and throat. The 
extent of irritation depends on the exposure amount and length of time exposed.   
Ammonia is classified non-flammable by the Department of Transportation.  Ammonia will burn, 
but only in a very narrow concentration level when accompanied with a constant ignition source. 
 
3. Worst case  and alternate case release scenarios including administrative and 
engineering controls to limit/ prevent acc 
idental release. 
 
Worst case scenario depicts continuous source leak from the Low Temperature Recirculator  
located inside the plant machine room.  This vessels normal operating level is 6,800 pounds of 
liquid ammonia,  approximately 25% of it's total capacity. Although the recirculator is capable of 
holding 27,000 pounds, this exceeds engineering controls which limit the liquid level. Considering 
the "catastrophic" possibility does exist for this vessel to release it's entire contents, engineering 
controls incorporated into the system would normally prevent such a release. 
 
    Worst case release scenario criteria for the Alliant Foodservice facility: 
 
    Ammonia Quantity:                  6,800 pounds 
    Rate of Release:                   680 lbs / min. (10 min. release) 
    LOC (Level of Concern):            200 ppm  (EPA ERPG-2)   
    Physical State:                    Gas  
          Type of Area:                     Urban 
    Wind Speed:                        1.5 m/sec 
 
   Distance to Endpoint                    2.6 miles 
 
Alternate release scenario is represented by the release of ammonia vapor from a safety relief 
valve (SRV) due to an over-pressurization condition on the high temperature recirculator vessel 
located within the Alliant Foodservice facility machine room. The indicated relief valve would be 
performing exactly as it is designed to do during an over-pressurization condition. Valve would 
open to relieve the over-pressure and vent into the atmosphere via the roof vent pipe. 
 
    Alternate case release scenario criteria for Alliant Foodservice facility: 
 
    Ammonia Quantity:                  310 pounds 
    Rate of Release:                          22 pounds/min. (27 min. release) 
    Wind Speed:                        3.0 m/sec. 
    Distance to Endpoint:                   .15 miles 
 
 
    The following administrative and engineering controls are in place at Alliant 
Foodservice. These controls are designed to eliminate, or reduce 
the possibilities of an 
accidental release from the refrigeration system. 
 
 
    *  Electronic ammonia detection installed in compressor room, distribution cooler, freezer 
areas and on the roof by the relief vent discharge. Alarm system activates a local audible alarm 
and security alert system to alert plant personnel of the potential ammonia leak in the monitored 
areas.  
 
    *  High level switches are configured to high and low pressure receivers and the  
intercooler. High level switches will shut down compressor operation during a high level 
condition. 
 
    * All compressors are configured with critical safety controls (high pressure, low pressure, 
high oil temp cut-outs, etc.) to shut down the respective compressor in the event of an abnormal 
operating condition. 
 
    *  Safety Relief Valves are configured to all pressure vessels, condensers and compressor 
oil separators to eliminate over pressurization conditions in those associated pieces of equipment. 
 
    *  Eme 
rgency "kill" buttons are installed by the machine room exit doors to enable system 
shutdown from outside the room in the event of an emergency involving the ammonia system. 
 
    *  Periodic Maintenance Program is in place within the maintenance department to ensure 
the refrigeration system and it's components are kept in optimum mechanical and operational 
status. 
 
 
4.  Five-year accident history. 
 
The Alliant Foodservice, Inc. facility at Detroit has had zero accidental releases to report.  
 
 
5.   Emergency Response Program 
 
The purpose of the Alliant Foodservice Emergency Action Plan is to: 
 
    1.   Minimize exposure to our employees and the surrounding community in the event of a 
    hazardous material release or spill. 
 
    2.  Assure the safe emergency evacuation of the plant in the instance that it is required. 
 
    3.  Provide for prompt medical attention to any employees who become seriously injured 
    or ill at work. 
 
    4.  Facility management has developed an Emerg 
ency Action Plan to ensure a fast and         
    efficient response in the event of  fire, natural disasters, bomb threat or an accidental 
    release of hazardous materials. 
 
Our Emergency Action Plan currently meets requirements as set forth in OSHA 29 CFR 1910.38, 
Employee Emergency and Fire Prevention Plans.
Click to return to beginning