Western Farm Service, Imperial - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

Agrium / Western Farm Service 
Imperial Facility 
 
 
1.  Facility Accidental Release Policy 
 
The owners, management, and employees of Western Farm Service's Imperial facility (herein referred to as the Facility) at 305 Larsen Road, Imperial, California, 92251 are committed to the prevention of any accidental release of anhydrous ammonia, and Nitrosol / aqua ammonia.  If an accidental release should occur, the facility is prepared to work with the local fire department, or other authorities to mitigate any release and minimize the impact of the release to people and the environment.  A detailed emergency response plan has been developed and will be implemented in the event of an accidental release. 
 
2.  Facility Information 
 
The primary activity at the Facility is the storage, blending, and sale of fertilizers, in addition to, the sale of pre-packaged agricultural chemicals to farmers.  
 
Anhydrous ammonia is received, stored, and distributed for both direct application and for blending int 
o mixed grade fertilizers for crop production nutrients.  
 
Anhydrous ammonia is stored in two 18,000-gallon, one 30,000-gallon and one 15,000-gallon storage tanks (bullets) at the site.  The maximum quantity of anhydrous ammonia handled in this process is 413,000 pounds. 
 
Nitrosol / Aqua ammonia (upto 20% of ammonia by weight) is stored in one 17,000-gallon, and one 735,000-gallon above ground tank at the site. The maximum quantity of Nitrosol / aqua ammonia handled is 7,144,000 pounds.  The total quantity of ammonia present in the aqua ammonia, based on 20% active ingredient by weight, is 1,428,800 pounds.   
 
3.  The Worst-Case Release Scenario and Alternative Release Scenario 
 
A.  Anhydrous Ammonia Alternative Release Scenarios   
The first alternative release scenario is failure of the largest storage tank when filled to the greatest amount releasing 130,000 pounds of anhydrous ammonia which represents the largest tank filled to 85% capacity as limited by regulations.  The distance t 
o the endpoint (point of dispersion to 200 ppm) is 2.60  miles.   The second alternative release scenario, based on the PHA scenarios (or the most likely potential incident) and  is a release of 11,908 pounds of anhydrous ammonia from a broken 2-inch diameter pipe.  The distance to the endpoint (point of dispersion to 200 ppm) is 1.18 miles. 
 
B.  Nitrosol / Aqua Ammonia Worst-Case and Alternative Release Scenarios   
The worst-case release scenario is failure of the largest storage tank when filled to the greatest amount would release 6,982,500 pounds of Nitrosol / aqua ammonia solution.  The distance to the endpoint (point of dispersion to 200 ppm) is 6.1 miles.  The alternative release scenario, based on the PHA scenarios (or the most likely potential incident) is a release of 10,000 pounds of Nitrosol / aqua ammonia solution from a storage tank modeled with an increased wind speed and "D" Stability modeling parameters.  The distance to the endpoint (point of dispersion to 200 ppm) is 
0.19 miles. 
 
4.  Accidental Release Prevention Program 
 
Anhydrous Ammonia and Nitrosol / Aqua Ammonia:  The Facility has implemented the provisions of the "Safety Requirements for Storage and Handling of Anhydrous Ammonia, K-61.1", published by the American National Standards Institute, Inc.; California Code of Regulations, Title 8, Subchapter 1, "Unfired Pressure Vessel Safety Orders"; and the standards of the U.S. Occupational Safety and Health Administration (OSHA), 29 CFR 1910.111, "Storage and Handling of Anhydrous Ammonia." 
 
5.  Five-year Accident History 
 
a. There have been no accidental releases or near misses of anhydrous ammonia or Nitrosol / aqua ammonia in the past five years that: 
 
1.  Have caused any deaths, injuries, or significant property damage at the facility; nor 
 
2.  Have resulted in off-site deaths, injuries, evacuations, sheltering in place, property  damage, or environmental damage. 
 
6.  The Emergency Response Program 
 
The facility's emergency response program  
was written in accordance with the following regulations: 
 
OSHA 29 CFR 1910.38; 
 
OSHA 29 CFR 1910.120; and 
 
Section 25503, Division 6.95 of the California Health and Safety Code 
 
7.  Planned Changes to Improve Safety 
 
Safety improvement is an on-going process at the facility.  Periodic evaluations are performed to assess the maintenance of safe conditions.  Specific planned changes to the anhydrous ammonia, and Nitrosol /  aqua ammonia processes at the facility are listed in the Facility PHAs. In summary, planned changes address the review and development of Standard Operating Procedures for regulated onsite processes.
Click to return to beginning