Farmers Union Co-op Services - Agronomy Plant - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

Risk Management Plan 
Executive Summary 
Clean Air Act Amendment, Section 112r 
Farmers Union Co-op Services 
 
ACCIDENTAL RELEASE PREVENTION AND EMERGENCY RESPONSE POLICIES 
The owners, management and employees of Farmers Union Co-op Services are committed to the prevention of any accidental release of anhydrous ammonia.  Farmers Union Co-op Services' policy is to adhere to all applicable Federal and State rules and regulations in order to: 
1. Prevent unnecessary human exposure, 
2. Reduce the threat to employees health, and  
3. To reduce the threat to nearby members of the community. 
Safety depends upon the manner in which an accidental release is handled, combined with the safety devices inherent in the design of the operation, the safe handling procedures used and the training of personnel. 
 
Farmers Union Co-op Services complies with the provision of "Safety Requirements for Storage and Handling of Anhydrous Ammonia, K-61-1", published by The American National Standards Institute, Inc., a 
nd the standards of the U.S. Occupational Safety and Health Administration (OSHA), 29 CFR 1910.111, "Storage and Handling of Anhydrous Ammonia".  Farmers Union Co-op Services' emergency response plan includes procedures for notification of the local fire authority, the LEPC and any potentially affected neighbors. 
 
STATIONARY SOURCES AND REGULATED SUBSTANCES 
 
Anhydrous Ammonia 
At this facility, anhydrous ammonia is stored and distributed for resale to farmers and other customers. 
 
Anhydrous ammonia is received by truck, and is stored in a 30,000-gallon tank.  The anhydrous ammonia is distributed and used for direct application. 
 
The maximum amount of anhydrous ammonia that can be stored at this facility is 119,000 pounds (30,000 gallons times 4.67 pounds/gallon times 85%). 
 
RELEASE SCENARIOS 
 
Anhydrous Ammonia 
Worst case scenario - Failure of the 30,000-gallon tank when filled to 85% capacity would release 119,000 pounds.  The anhydrous ammonia would be released as a gas over a 10-minut 
e period (11,908 pounds per minute).  The distance to the endpoint under urban conditions using RMP-Comp (toxic endpoint is 200 ppm) is 3.6 miles. 
 
Alternate Scenario - A hose breaks resulting in a release of 5% of the tank or 6000 pounds.  The release is stopped through human intervention in 2 minutes (3,000 lbs/min).  The distance to the endpoint under urban condition is 0.4 miles. 
 
GENERAL ACCIDENTAL RELEASE PREVENTION PROGRAM AND THE SPECIFIC PREVENTION STEPS 
This distribution facility complies with EPA's Accidental Release Rule and with all applicable state codes and regulations. 
 
The anhydrous ammonia facility has implemented the provision of "Safety Requirements for Storage and Handling of Anhydrous Ammonia, K-61.1", published by The American National Standards Institute, Inc., and the standards of the U.S. Occupation Safety and Health Administration (OSHA), 29 CFR 1910.111, "Storage and Handling of Anhydrous Ammonia". 
 
FIVE-YEAR ACCIDENT HISTORY 
There have been no accidental re 
leases of anhydrous ammonia in the past 5 years that have caused any death, injuries, or significant property damage at the facility; nor to our knowledge, have resulted in off site deaths, injuries, evacuation, sheltering in place, property damage or environmental damage. 
 
EMERGENCY RESPONSE PROGRAM 
This facility emergency response program is written in accordance with OSHA standard 29 CFR 1910.38.   Farmers Union Co-op Services has discussed this program with the LEPC and local fire department.  A representative of the local fire department has inspected the site. 
 
PLANNED CHANGES TO IMPROVE SAFETY 
Safety improvement is an on-going process at the facility.  Periodic evaluations are performed to assess the maintenance of safe conditions.  There are no additional specific safety recommendations for implementation.
Click to return to beginning