Yauco Filtration Plant - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

Compania de Aguas de Puerto Rico (CAPR) as operator of the Puerto Rico Aqueduct & Sewer Authority (PRASA) system has developed a Risk Management Plan (RMP) for management and prevention of risks associated with the storage and use of chlorine, a regulated toxic substance, at the Yauco Water Filtration Plant.  The RMP was prepared in compliance with 40 CFR Part 68 and Clean Air Act (CAA) Section 112(r)(1).  The Prevention Program elements build upon the facility's Process Safety Management (PSM) system prepared in compliance with 29 CFR Part 1910.119. 
 
Accidental Release Prevention and Emergency Response Policies 
 
It is CAPR's policy to comply with applicable Federal and Puerto Rican requirements.  The chlorination process at the Yauco Water Filtration Plant uses chlorine, a hazardous toxic substance regulated by EPA, OSHA, and PROSHO.  Due to the hazardous characteristics of chlorine, the Yauco Water Filtration Plant observes various safety precautions in the storage, conveyance and us 
e of chlorine.  The safety precautions are necessary to protect employees, contractors, and visitors at the Yauco Water Filtration Plant and the immediately surrounding areas.  Safety precautions include procedures and equipment to minimize the potential for accidental release, as well as a written emergency response program for response to any chlorine release that may occur. 
 
The Stationary Source and Regulated Substances Handled 
 
The Yauco Water Filtration Plant supplies up to 2.6 million gallons per day of water to the surrounding community.  Chlorine is used to disinfect the water, destroying microorganisms that could cause illness in humans. 
 
Chlorine is delivered to the facility via truck in 150 pound cylinders.  The storage building has space for up to nine full cylinders, a total of 1,350 pounds of chlorine.  Chlorine cylinders are connected to vacuum chlorinators.  The chlorinators regulate chlorine use.  From the chlorinators, chlorine gas is distributed under vacuum to inje 
ctors.  The injectors combine the gaseous chlorine with water.  The chlorinated water is mixed with the water plant flow for disinfection. 
 
Worst-case and Alternative Release Scenarios 
 
The worst-case release scenario was determined following EPA's Risk Management Program Offsite Consequence Analysis Guidance.  The worst-case release scenario is a vapor release of the entire contents of a 150 pound cylinder over a ten minute period (15.0 pounds of chlorine per minute).  Other worst-case assumptions required by EPA include a low wind speed (1.5 meters per second), stable atmosphere (Class F), urban topography, and no active mitigation of the release.  The storage room enclosure would provide passive mitigation of the release. 
 
EPA requires the determination of the area (zone of vulnerability) which may be exposed to a chlorine concentration of 3 ppm or greater.  According to the American Industrial Hygiene Association, 3 ppm is the maximum concentration of chlorine in air below which ne 
arly all people could be exposed for one hour without serious health effects.  Based on the worst-case assumptions, the zone of vulnerability was determined to extend 0.3 mile from the chlorine storage area. 
 
The following are known to be within the zone of vulnerability for the worst-case release scenario: schools, residences and recreational areas. 
 
Approximately 120 residents are located within a 0.3 mile radius of the chlorine storage area.  Many of these residents would not actually be impacted in even a worst-case release, as the chlorine would travel in the direction of wind.  No known environmental receptors (such as state parks or officially designated wildlife preserves) are located within the zone of vulnerability.  The conditions and parameters for the worst-case scenario are specified by EPA. 
 
A more realistic alternative release scenario was examined, also following EPA's Risk Management Program Offsite Consequence Analysis Guidance.  The alternative release scenario is a 
vapor release of the entire contents of a 150 pound cylinder over a ten minute period (15.0 pounds of chlorine per minute).  More typical weather conditions are used (wind speed of 3.0 meters per second, atmospheric stability Class D).  Other conditions remain the same as in the worst-case scenario (urban topography, passive mitigation of the release by the storage room enclosure). 
 
The zone of vulnerability for the alternative release scenario is determined to extend 0.1 mile from the chlorine storage area.  Approximately 10 residents are located within a 0.1 mile radius of the chlorine storage area.  These residents could be impacted, depending on the direction of wind.  No known environmental receptors are located within the zone of vulnerability. 
 
General Accidental Release Prevention Program and Chemical-specific Prevention Steps 
 
CAPR complies with PROSHO requirements for Prevention Programs and for Process Safety Management.  Operators, maintenance staff and contractors are inf 
ormed of chlorine hazards, and hazard signs are posted in the chlorine storage area.  Standard operating and maintenance procedures have been developed, and employees who work with chlorine are provided training. 
 
Emergency Response Program 
 
CAPR has an emergency response program.  Chlorine gas detectors are located within the storage area for early detection and warning of any leak.  Leak repair kits are maintained on site, and operators are trained in how to quickly stop any leak that may occur.  The emergency response program is coordinated with Civil Defense for notification of the public. 
 
CAPR periodically conducts various training programs, including emergency response training.  This CAPR facility is scheduled to receive refresher training by 09/13/2000. 
 
Five-year Accident History 
 
One accident resulting in the unplanned release of chlorine gas in excess of 10 pounds has been recorded in the past five years.  On July 16, 1997 there was a release of an estimated 30 pounds from  
a valve.  No injuries resulted from this leak.  The cause of this leak was investigated and equipment was repaired to prevent further releases. 
 
Planned Changes to Improve Safety 
 
CAPR uses Process Hazard Analyses (PHA) to identify and recommend changes to ensure a high level of safety.  Issues identified from a PHA are then addressed in CAPR's Prevention Program.  Assessments of the chlorine processes were conducted during April, May and December 1999 for each CAPR facility.  Documentation of the formal PHA for this facility was completed on 03/02/2000.  An audit of the RMP and PSM programs will be conducted within three years to verify the effectiveness of the program.
Click to return to beginning