Gas Supply Resources, Inc. - Albany Terminal - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

General Executive Summary for Propane Storage Distribution Facility 
Gas Supply Resources, Inc. - Albany Terminal 
 
1.  Accidental Release Prevention and Emergency Response Policies: 
 
The primary function of Gas Supply Resources, Inc. - Albany Terminal is to act as a propane distribution  
facility.  By virtue of the flammable effects associated with propane, it is necessay to observe certain  
safety precautions in handling propane to prevent unnecessary human exposure, to reduce the threat to  
our own personal health as well as the health of our co-workers, and to reduce the threat to nearby  
members of the community.  We are strongly committed to employee, public, and environmental safety.   
Safety at our facility depends upon the manner in which we handle propane as well as on the various  
safety devices incoprporated into the design of our equipment.  Furthermore, comprehensive training  
received by our employees adds to the safety of our distribution facility. 
Our emergency response  
program is based upon the NPGA's LP-Gas Safety Handbook/ Guidelines for  
Developing Plant Emergency Procedures/ How to Control LP-Gas Leaks and Fires.  In addition to the  
presence of appropriate controls to prevent possible releases of propane, if a release does occur, we  
are completely coordinated with the Albany Fire Department, which provides highly trained emergency  
response personnel to control and mitigate the effects of the release. 
 
2.  The Stationary Source and the Regulated Substance Handled: 
 
The primary purpose of this facility is to repackage and distribute propane to wholesale customers for use  
as a fuel.  Propane arrives at our facility via rail car and transport and is stored in three (3) storage tanks.   
This facility has equipment for unloading rail cars and transports and to load transports.  Access to this  
site is restricted to authorized facility employees, authorized management personnel and authorized  
contractors. 
The regulated substance handled at this fac 
ility is propane.  The maximum amount of propane that can be  
stored at this facility is 997,920 lb. 
 
3.  The Flammable Worst Case Release Scenario and the Alternative Release Scenario, Including Administrative Controls and Mitigation Measures to Limit the Distance for Each Reported Scenario: 
 
We have calculated the worst case release scenario based on EPA's RMP Comp(TM) method.  The alternative release scenario analysis is based on EPA's RMP Com (TM) method.  The following paragraphs provide details of the chosen scenarios. 
The worst case release scenario submitted for propane involves a catastrophic release from the storage  
tanks.  The scenario involves the release of 997,920 lb. of propane.  The release quantity has been  
calculated with a wind speed of 1.5 meters/second, stability class:F and an air temerature of 25 degrees  
C.  The estimated distance to 1 psi overpressure is .8 miles. 
 
The alternative release scenario involves a release from the rail tower header piping resulting 
in a vapor  
cloud fire.  In this scenario 2100 pounds of propane is released in one minute.  This release is also  
controlled by active mitigation measures that include monitor fire nozzles, emergency shutdown valves,  
and manual valves.  With a wind speed of 3 meters/second, stability class: D and an air temperature of 25  
degrees C.,  the estimated distance to lower flammability limit is < 0.1 miles. 
 
4.  The General Accidental Release Prevention Program and the Chemical-Specific Prevention Steps: 
 
Our facility has taken all the necessary steps to comply with the accidental release prevention  
requirements set out under 40 CFR part 68 of the EPA.  This facility was designed and constructed in  
accordance with NFPA-58 Standard, 1995 Edition and NFPA-70, 1993 Edition. 
The following sections briefly describe the release prevention program that is in place at our stationary  
source. 
 
Safety Information: 
 
Gas Supply Resources, Inc. - Albany Terminal maintains a detailed record of written 
safety information,  
which describes the chemical hazards, operating parameters and equipment designs associated with all  
aspects of our distribution facility. 
 
Hazard Review: 
 
A visual inspection methodology is used to carry out hazard reviews at our facility.  The reviews focus on  
operating procedures, equipment functions, and handling pratices to identify possible hazards.  Any 
finding related to the hazard reviews are addressed in a safe and timely manner. 
 
Operating Procedures: 
 
For the purposes of conducting safety activities within our covered processes, Gas Supply Resources,  
Inc. - Albany Terminal maintains written operating procedures.  These procedures address various modes  
of operation such as emergency shutdown system/ startup procedures, pre-operational visual inspection  
procedures, rail car unloading procedures, transport loading procedures, transport unloading procedures,  
and emergency shutdown system/ shutdown procedures.  The information is regularly reviewed an 
d is  
readily accessible to operators involved with the processes. 
 
Training: 
 
Gas Supply Resources, Inc. - Albany Terminal has a comprehensive training program in place to ensure  
that employees are completely competent in the operating procedures  
associated with these processes.  New employees receive basic training in process operations followed  
by on-the-job supervision until they are deemed competent to work independently and have passed a  
written proficiency test.  Refresher training is provided yearly. 
 
Maintenance: 
 
Gas Supply Resources, Inc. - Albany Terminal carries out documented maintenance checks on process  
equipment to ensure proper functioning.  Maintenance activities are carried out by qualified personnel with  
previous training in these practices.  Furthermore, personnel are offered specialized training as needed.   
Any equipment deficiencies identified by the maintenance checks are corrected in a safe and timely manner. 
 
Compliance Audits: 
 
Gas Supply Resources, I 
nc. - Albany Terminal conducts audits on a regular basis to determine whether  
the provisions set out under the RMP rule are being implemented.  These audits are carried out at least  
every 3 years and any corrective actions required as a result of the audits are undertaken in a safe and  
prompt manner. 
 
Incident Investigation: 
 
Gas Supply Resources, Inc. - Albany Terminal promptly investigates any incident that has resulted in, or  
could reasonably result in, a catastrophic release of propane.  These investigations are undertaken to  
identify the situation leading to the incident as well as any corrective actions to prevent the release from  
recurring.  All reports are retained for a minimum of 5 years. 
 
5.  Five-year Accident History: 
 
Gas Supply Resources, Inc. - Albany Terminal has had an excellent record of preventing accidental  
releases over the last 5 years.  Due to our stringent release prevention policies, there has been no  
accidental release during this period. 
 
6.  Emergen 
cy Response Plan: 
 
Gas Supply Resources, Inc. - Albany Terminal has a written emergency response plan to deal with  
accidental releases of propane.  The plan includes all aspects of emergency response including  
evacuations and notification of local emergency response agencies. 
Our facility's emergency response plan is based upon the NPGA's LP-Gas Handbook/ Guidelines for  
Developing Plant Emergency Response Procedures/ How to Control LP-Gas Leaks and Fires. 
To ensure proper functioning, our emergency response equipment is regularly inspected and serviced.  In  
addition, the plan is promplty updated to reflect any pertinent changes taking place within our processes  
that would require a modified emergency response. 
 
7.  Planned Changes to Improve Safety: 
 
Several developments and findings have resulted from the implementation of the various elements of our  
accidental release prevention program.  Continued operator training, employee CTEP certification, and operational reviews are some 
of the major steps we want to take to improve safety at our facility.  These changes shall be implemented on an ongoing basis. 
 
8.  Certification Statement: 
 
The undersigned certifies that to the best of my knowledge, information, and belief, formed after  
reasonable inquiry, the information submitted is true, accurate and complete. 
 
Name:  James L. Peschong 
Signature: 
Title: Director of Engineering Services 
Date signed: June 9, 2000
Click to return to beginning