Oran Ag Service - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

Risk Management Plan - Executive Summary 
 
Facility: United Suppliers, Inc., Oran, Iowa   
Contact:  Gary Zimmermann 
Phone:  319-638-7551 
 
    1.   Facility Policy. 
 
    The owners, management and employees of Oran Ag Service are committed to the 
    prevention of any accidental releases of Anhydrous Ammonia.       
    If an accidental release should occur, the facility is prepared to work with the local fire 
    department, or other authorities, to mitigate and minimize the impacts of the release to 
    the people and the environment.   
 
    2.   Facility Information. 
 
    The primary activity at the facility is the storage and blending of fertilizers for sale to 
    farmers.  Anhydrous ammonia is received, stored and distributed for both direct 
    application and for blending into mixed-grade fertilizers for crop production nutrients. 
 
    Anhydrous ammonia is stored at the facility in (1) one 12,000 gallon storage tanks.  The 
    maximum quantity stored of anhy 
drous ammonia is 53,440 pounds.   
 
 
3.   Worst-Case Scenario and Alternate Release Scenario 
 
         a.   The worst-case scenario would be the release of the total contents of a storage 
         tank released as gas over a period of 10 minutes.  The maximum quantity released 
         would be 53,440 pounds, which represents the volume of the largest storage tank 
         at 85 percent capacity as limited by design standards.  The distance to the end 
         point (point of dispersion to 200 parts per million, or ppm) is 1.5 miles.   
 
         b.   The alternate release scenario, based on the five-year accident history (or the most 
         likely potential incident), is a release from a break in a transfer hose.  The distance 
         to the endpoint (point of dispersion to 200 ppm) is 1.3 miles.   
 
4.   Accidental Release Prevention Program 
 
    The facility has been reviewed for general compliance with the provisions of "Safety 
    Requirements for the Stor 
age and handling of Anhydrous Ammonia, K-61.1", published 
    by The American National Standards Institute, Inc. (ANSI), and the standards of the U.S. 
    Occupational Safety and Health Administration (OSHA), 29 CFR 1910.111, "Storage and 
    handling of anhydrous ammonia".  The ANSI Standard has been adopted by reference by 
    Iowa Administrative Code Part 21 Chapter 43 Rule 43.6(200)-Standard for the storage 
    and  handling of anhydrous ammonia.  The OSHA standard is referenced in the 
    Registration Form Section 8.3.b. 
 
5.   Five-Year Accident History.         
 
    There have been no accidental releases of anhydrous ammonia or propane in the past five 
    years that: have caused any deaths, injuries or significant property damage at the facility; 
    nor to our knowledge, have resulted in off-site deaths, injuries, evacuations, sheltering in 
    place, property damage, or environmental damage.   
 
 
6.   Emergency Response Program. 
 
    The facility has: 
 
 
a.   a written action plan, in accordance with OSHA standard 29 CFR 1910.38; 
 
         b.   provided state and local authorities with the emergency planning and community 
         right-to-know information as required under SARA Title III (EPCRA); 
 
          c.   a written emergency response program, in accordance with OSHA standard  
                   29 CFR 1910.120, including pre-emergency planning and employee training. 
 
7.   Planned Changes to Improve Safety. 
 
    Safety improvement is an on-going process at the facility.  Periodic evaluations are 
    performed to assess the maintenance of safe conditions.   
 
    There are no additional specific safety recommendations regarding storage or use of 
    anhydrous ammonia for implementation at this time.
Click to return to beginning