CENTRAL CO-OP - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

CENTRAL CO-OP 
P.O. BOX 515 
BLOOMING PRAIRIE, MN. 55917 
 
FOR FURTHER INFORMATION CONTACT CHUCK WAGNER, PLANT MANAGER 507-583-6661 
 
RISK MANAGEMENT PLAN-EXECUTIVE SUMMARY 
 
1. FACILITY POLICY 
 
THE OWNERS, MANAGEMENT, AND EMPLOYEES OF CENTRAL CO-OP ARE COMMITTED TO THE PREVENTION OF ANY ACCIDENTAL RELEASES OF ANYHYDROUS AMMONIA. IF AN ACCIDENTAL RELEASE SHOULD OCCUR, THE FACILITY IS PREPARED TO WORK WITH THE LOCAL FIRE DEPARTMENT, OR OTHER AUTHORITIES, TO MIITIGATE ANY RELEASE AND MINIMIZE THE IMPACT OF THE RELEASE TO PEOPLE AND THE ENVIRONMENT. 
 
2. FACILITY INFORMATION 
 
THE PRIMARY ACTIVITY AT THE FACILITY IS THE STORAGE AND BLENDING OF FERTILIZERS FOR SALE TO FARMERS. 
 
ANHYDROUS AMMONIA IS RECEIVED, STORED AND DISTRIBUTED FOR DIRECT APPLICATION. ANHYDROUS AMMONIA IS USED FOR CROP PRODUCTION NUTRIENTS. 
 
THE MAXIMUM QUANTITY OF AMMONIA STORED WOULD BE 503,000 POUNDS IN OUR (2) 30,000 GALLON STORAGE TANKS AND NURSE TANKS. THE MAXIMUM QUANTITY HANDLED WOULD BE THE UNLOADING OF A TANK TRUCK H 
OLDING 40,000 POUNDS. 
 
 
 
3. THE WORST- CASE RELEASE SCENARIO AND THE ALTERNATIVE RELEASE SCENARIO. 
 
A. THE WORST-CASE RELEASE SCENARIO FOR ANHYDROUS AMMONIA WOULD BE RELEASE OF THE TOTAL CONTENTS OF A STORAGE TANK RELEASED AS A GAS OVER TEN MINUTES. THE MAXIMUM QUANTITY RELEASED WOULD BE 130,000 POUNDS WHICH REPRESENTS THE VOLUME OF THE STORAGE TANK AT 85%  CAPACITY AS LIMITED BY DESIGN STANDARDS. THE DISTANCE TO THE END POINT (POINT OF DISPERSION TO 200 PPM) IS 1.12 MILES. 
 
 
 
B. THE ALTERNATIVE RELEASE SCENARIO FOR ANHYDROUS AMMONIA BASED ON THE HAZARD REVIEW IS A 2 MINUTE RELEASE FROM A BREAK IIN A 3 INCH PIPE. THE DISTANCE TO THE ENDPOINT (POINT OF DISPERSION TO 200 PPM) IS .78 MILES. 
 
 
4. THE ACCIDENTAL RELEASE PREVENTION PROGRAM. 
 
THE FACILITY HAS IMPLEMENTED THE PROVISIONS OF "SAFETY REQUIREMENTS FOR THE STORAGE AND HANDLING OF ANHYDROUS AMMONIA, K-61.1", PUBLISHED BY THE AMERICAN NATIONAL STANDARDS INSTITUTE, INC. AND THE STANDARDS OF THE U.S. OCCUPATIONAL SAFETY AND HEALTH ADM 
INSTRATION (OSHA), 29 CFR 1910.111,"STORAGE AND HANDLING OF ANHYDROUS AMMONIA". IN ADDITION,  MINNESOTA DEPT. AG RULES.  
 
5. THE FIVE-YEAR ACCIDENT HISTORY. 
 
A. THERE HAVE BEEN NO ACCIDENTAL RELEASES OF ANHYDROUS AMMONIA OR PROPANE IN THE PAST FIVE YEARS THAT: 
 
HAVE CAUSED ANY DEATHS, INJURIES, OR SIGNICANT PROPERTY DAMAGE AT THE FACILITY: NOR TO OUR KNOWLEDGE, HAVE RESULTED IN OFFSITE DEATHS, INJURIES, EVACUATIONS, SHELTERING IN PLACE, PROPERTY DAMAGE OR ENVIRONMENTAL DAMAGE. 
 
6. THE EMERGENCY RESPONSE PROGRAM. 
 
THE FACILITY HAS: 
 
A. A WRITTEN EMERGENCY ACTION PLAN, IN ACCORDANCE WITH OSHA STANDARD, 29 CFR 1910.38: 
 
B. PROVIDED STATE AND LOCAL AUTHORITIES THE EMERGENCY AND COMMUNITY RIGHT-TO- KNOW INFORMATION AS REQUIRED UNDER SARA TITLE III (EPCRA). 
 
C. COORDINATED WITH LOCAL EMERGENCY RESPONDERS. 
 
7. PLANNED CHANGES TO IMPROVE SAFETY. 
 
SAFETY IMPROVEMENT IS AN ON-GOING PROCESS AT THE FACILITY.  PERIODIC EVALUATIONS ARE PERFORMED TO ASSESS THE MAINTENANCE OF SAFE CONDITIONS.  THERE A 
RE NO ADDITIONAL SPECIFIC AMMONIA OR PROPANE SAFETY RECOMMENDATIONS FOR IMPLEMENTATION AT THIS TIME.
Click to return to beginning