Herrin, LTD - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

Herrin, LTD 
 
13962 Old Rt. 36 
 
Buffalo, IL  62515 
 
Risk Management Plan 
EXECUTIVE SUMMARY 
 
1. The Facility Policy 
 
The owners, management, and employees of Herrin, LTD are committed to the prevention of any accidental release of anhydrous ammonia.  If an accidental release should occur, the facility is prepared to work with the Buffalo Fire Dept., Sanagmon Co. LEPC or other authorities, to mitigate any release and minimize the impact of the release to people and the environment. 
 
2. Stationary Sources and Regulated Substances 
 
The primary activity at the facility is the storage and blending of fertilizers, farm chemicals and related agricultural products, for sale to the farmer. 
 
The maximum quantity of Anhydrous Ammonia stored would be 130000 gallons (or 607516 lbs.) in our Two storage tank(s), consisting of 2x Rail Cars and 2x 30,000 storage tanks. The maximum quantity handled in the largest tank would be the is a Rail Car (80 ton.) on the siding holding 163562 pounds. 
 
3. The Worst- 
Case Release Scenario and the Alternative Release Scenario. 
 
Worse-Case:  The worse-case scenario would be the release of the total contents of a storage tank (or rail tank car) released as a gas over 10 minutes.  The maximum quantity released would be 163562 pounds, which represents the volume of the largest storage tank at 85% capacity as limited by design standards.  The distance to the endpoint (point of dispersion to 200 ppm) is 1.8 miles, which would encompass an area of 10.17 sq. miles, with the potential of impacting approximately 550 souls in the surrounding area. 
 
Alternative Case:  The alternative release scenario is based on the five-year accident history (or the most likely potential incident) is a release from a break in a 3 inch Diameter transfer hose.  The distance to the endpoint (point of dispersion to 200 ppm) is 0.83 miles, which would encompass an area of 2.16 sq. miles, with the potential of impacting approximately 10 souls in the surrounding area. 
 
4. The Acciden 
tal Release Prevention Program 
 
This facility has implemented the provisions of "Safety Requirements for the Storage and Handling of Anhydours Ammonia, K-61.1", published by The American National Standards, Institute, Inc., and the standards of the U.S. Occupational Safety and Health Administration (OSHA), 29 CFR 1910.111, "Storage and handling of Anhydrous Ammonia". 
 
5. The Five-year Accident History 
 
There have been no accidental releases of Anhydrous Ammonia (from our fixed sources) in the past five years that: have caused deaths, injuries, or significant property damage at this facility; nor to our knowledge, have resulted in offsite deaths, injuries, evacuations, sheltering in place, property damage, or environmental damages.  We did have a pull-away break in a transfer vapor line that was connected to a rail car. This release occurred on 9-3-1997 at 21:30 Hrs.  The release lasted 1 minute and released a volume of Ammonia estimated to be 85 lbs..  There were no injuries and no off 
-site involvement.  The fire department was called and informed of the release.  We have changed our tank car marking procedures and have had no further incidents as of this date. 
 
6. The Emergency Response Program 
 
This facility has a current Emergency Action Plan ( in accordance with OSHA standard, 29 CFR 1910.38) in place and has coordinated this program with  Fire Chief. of Buffalo Fire Dept. and with  of Sanagmon Co. LEPC.  We train our staff on the elements found in our response program (in accordance with OSHA standard, 29 CFR 1910.120) and have invited the fire department to visit our facility in order to provide them with a working knowledge of our plant's layout and our storage facility. This facility has provided state and local authorities the emergency planning and community right-to-know information as required under SARA Title III (EPCRA). 
 
7. Planned Changes to Improve Safety. 
 
Safety improvement is an on-going process at the facility.  Periodic evaluations are performe 
d to assess the maintenance of safe conditions.  There are no additional specific anhydrous ammonia safety recommendations for implementation at this time.