HUMBOLDT- ST. VINCENT ELEV. - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

HUMBOLDT-ST.VINCENT ELEV 
RR1 BOX 98 
ST. VINCENT, MN. 56755 
 
 
FOR FURTHER INFORMATION, CONTACT AARON HUGHES, ASST. MANAGER, PHONE NUMBER  
218-823-6469. 
 
RISK MANAGEMENT PLAN-EXECUTIVE SUMMARY 
 
1. THE FACILITY POLICY 
 
   THE OWNERS, MANAGEMENT, AND EMPLOYEES OF HUMBOLDT-ST.VINCENT ELEV. ARE 
COMMITTED TO THE PREVENTION OF ANY ACCIDENTAL RELEASES OF ANHYDROUS AMMONIA. IF AN 
ACCIDENTAL RELEASE SHOULD OCCUR, THE FACILITY IS PREPARED TO WORK WITH THE LOCAL FIRE 
COMPANY, OR OTHER AUTHORITIES,TO MITIGATE ANY RELEASE AND MINIMIZE THE IMPACT OF THE 
RELEASE TO PEOPLE AND THE ENVIRONMENT. 
 
2. FACILITY INFORMATION 
 
   THE PRIMARY ACTIVITY AT THE FACILITY IS THE STORAGE AND SALE TO FARMERS. 
 
    ANHYDROUS AMMONIA IS RECEIVED, STORED AND DISTRIBUTED FOR DIRECT APPLICATION. 
ANHYDROUS AMMONIA IS USED FOR CROP PRODUCTION NUTRIENTS. 
 
    THE MAXIMUM QUANTITY OF AMMONIA STORED WOULD BE 420,000 POUNDS IN OUR 
30,000 AND 26,000 GALLON STORAGE TANKS. THE MAXIMUM QUANTITY HANDLED WOULD BE 
THE UNLOADING OF A 
TANK TRUCK HOLDING 40,000 POUNDS. 
 
3. THE WORST-CASE RELEASE SCENARIO AND THE ALTERNATIVE RELEASE SCENARIO. 
 
A.  THE WORST-CASE SCENARIO FOR ANHYDROUS AMMONIA WOULD BE THE RELEASE OF 
THE TOTAL CONTENTS OF A STORAGE TANK RELEASED AS A GAS OVER TEN MINUTES. THE 
MAXIMUM QUANTITY RELEASED WOULD BE 130,000 POUNDS, WHICH REPRESENTS THE VOLUME 
OF THE STORAGE TANK AT 85 PERCENT CAPACITY AS LIMITED BY DESIGN STANDARDS. THE 
DISTANCE THE ENDPOINT (POINT OF DISPERSION TO 200 PPM) IS 1.12 MILES. 
 
B.   THE ALTERNATIVE RELEASE SCENARIO FOR ANHYDROUS AMMONIA BASED ON THE HAZARD 
REVEIW IS A 2 MINUTE RELEASE FROM A BREAK IN A 3 INCH PIPE. THE DISTANCE TO THE 
ENDPOINT (POINT OF DISPERSION TO 200 PPM) IS .78 MILES. 
 
4.   THE ACCIDENTAL RELEASE PREVENTION PROGRAM. 
 
     THE FACILITY HAS IMPLEMENTED THE PROVISIONS OF "SAFETY REQUIREMENTS FOR THE 
STORAGE AND HANDLING OF ANHYDROUS AMMONIA, K-61.1", PUBLISHED BY THE AMERICAN 
NATIONAL STANDARDS INSTITUTE, INC. AND THE STANDARDS OF THE U.S. OCCUPATIONAL SAFETY 
 
AND HEALTH ADMINISTRATION (OSHA) , 29 CFR 1910.111, "STORAGE AND HANDLING OF 
ANHYDROUS AMMONIA".  IN ADDITION, MINNESOTA DEPT. OF AG RULES.  
 
5.   THE FIVE YEAR ACCIDENT HISTORY. 
 
   A. THERE HAVE BEEN NO ACCIDENTAL RELEASES OF ANHYDROUS AMMONIA IN THE PAST 
FIVE YEARS THAT: 
        HAVE CAUSED ANY DEATHS, INJURIES, OR SIGNIFICANT PROPERTY DAMAGE AT THE FACILITY; 
NOR TO OUR KNOWLEDGE, HAVE RESULTED IN OFFSITE DEATHS, INJURIES, EVACUATIONS, 
SHELTERING IN PLACE, PROPERTY DAMAGE OR ENVIRONMENTAL DAMAGE. 
 
6.    THE EMERGENCY RESPONSE PROGRAM. 
 
      THE FACILITY HAS: 
 
A.   A WRITTEN EMERGENCY ACTION PLAN, IN ACCORDANCE WITH OSHA STANDARD,29 CFR 
1910.38; 
 
B.    PROVIDED STATE AND LOCAL AUTHORITIES THE EMERGENCY PLANNING AND COMMUNITY 
RIGHT-TO-KNOW INFORMATION AS REQUIRED UNDER SARA TITLE III (EPCRA). 
 
C.    COORDINATED WITH LOCAL EMERGENCY RESPONDERS. 
 
7.    PLANNED CHANGES TO IMPROVE SAFETY. 
 
      SAFETY IMPROVEMENT IS AN ON-GOING PROCESS AT THE FACILITY.  PERIODIC EVALUATIONS 
ARE PER 
FORMED TO ASSESS THE MAINTENANCE OF SAFE CONDITIONS. THERE ARE NO ADDITIONAL 
SPECIFIC ANHYDROUS AMMONIA SAFETY RECOMMENDATIONS. FOR IMPLEMENTATION AT THIS 
TIME.
Click to return to beginning