Schmitt Fertilizer Corporation, Farm - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

Schmitt Fertilizer Corporation 
Waucoma, Iowa 
Farm location 
Risk Management Plan - Executive Summary 
 
The accidental release prevention policy at Schmitt Fertilizer Corporation involves, but is not limited to technologies, procedures, and management practices.  All applicable procedures of the ANSI K-61.1 - 1989 revision of the "Safe Requirements for the Storage and Handling of Anhydrous Ammonia," as adopted by the Iowa Department of Agriculture and Land Stewardship (IDALS) are adhered to.  Our emergency response policy involves the emergency response services available in our community. 
 
This facility is in the business of selling anhydrous ammonia to farm customers as a form of nitrogen fertilizer.  The facility has one anhydrous ammonia storage tank with a total capacity of 18,000 gallons water capacity.  The storage tanks, several anhydrous ammonia nurse tanks, risers for filling nurse tanks, electrical panels, lighting, and safety equipment are all parts of this facility's anhydrou 
s ammonia operation.  The facility is manned only periodically during the season and is operational at ramdom hours. 
 
The off-site consequences analysis includes two anhydrous ammonia release scenarios, identified as "worst-case" release and "alternative" release scenario.  The first scenario is defined by EPA and shall assume the maximum quantity of a vessel is released as a gas in 10 minutes due to a catastrophic break.  The alternative release scenario is defined as a more likely accidental release of anhydrous ammonia caused by a transfer hose failure. 
 
The "worst-case" release scenario involves a catastrophic failure of the tank releasing the entire 85,000 pounds of anhydrous ammonia.  The off site consequences were calculated using "TFI's RMP Guidance for Ammonia Retailers".  The worst case scenario used EPA's recommended wind speed of 1.5 meters per second with an "F" atmospheric stability class.  A rural topography was selected as typical.  The distance to the endpoint was 2.18 
miles. It is estimated that 138 people would be affected by this release. 
 
 
The "alternative release" scenario assumed a hose breaks and leaks 7,200 pounds of anhydrous ammonia.  The EPA recommended wind speed of 3.0 meters per second with a "D" atmospheric stability class was used in this scenario.  Using rural topography and "TFI's RMP Guidance for Ammonia Retailers" the toxic endpoint is .92 mile.  The population with in that area is estimated to be 69 people.  The assumption is that the duration of the release is 2 minutes because equipment, excess flow valves, and human intervention will stop the leak.   
 
Schmitt Fertilizer Corporation has had no anhydrous ammonia leaks within the past five years.  Even though the company has had no releases it still coordinates annual visits with the local fire department to review the systems and procedures for response to a leak. 
 
Schmitt Fertilizer Corporation has several key elements in its accident prevention plan: 
1. The anhydrous ammonia  
system adheres to the laws and regulations that are based on the 1989 revision of the ANSI K61.1 adopted in 1990 by the State of Iowa. 
2. Annual training is required of all personnel on handling, transferring, or transporting anhydrous ammonia.  The training includes properties of ammonia, safe handling practices, first aid, and emergency response. 
3. Use of good management practices as specified by industry standards and training aids. 
4. Frequent site inspections by management and safety consultants. 
5. Annual inspections by IDALS fertilizer inspectors include safety equipment, tanks, and handling equipment. 
6. Use of proper anhydrous ammonia personal protective equipment and safety equipment. 
Changes are made in the system when necessary or when required by regulation change.  Periodic evaluations of the procedures help to determine whether or not a change in operations should be made to provide increased safety to the operators and to the community.
Click to return to beginning