COS Samoa Packing Company - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

The COS Samoa Packing Company is a tuna cannery that contains refrigerated areas.  The refrigerated areas are cooled by an anhydrous ammonia refrigeration system.  Anhydrous ammonia, a substance regulated by EPA, is one of the most economical refrigerants available.  However, the properties of ammonia makes it necessary to observe certain safety precautions while operating the refrigeration system to prevent employee exposure and to reduce the threat of exposure to nearby members of the community. 
 
   The COS Samoa Packing Company chose to follow the EPA's Chemical Accident Prevention Rule, Program Level 3, to prevent a release of ammonia from the refrigeration system.  The amount of ammonia estimated to be contained inside the refrigeration system is 11,000 pounds. 
 
   The COS Samoa Packing Company complies with EPA's Accidental Release Prevention Rule, and applicable state codes and regulations to prevent a catastrophic release of ammonia.  The ammonia refrigeration system has been const 
ructed according to the International Institute of Ammonia Refrigeration guidelines (IIAR).  The operators of the systems are required to complete a training and certification program to operate the ammonia refrigeration system. 
 
   The Accidental Release Prevention Program does not guarantee against an accidental release.  An offsite consequence analysis was completed using a computer model to simulate a release of the ammonia from the refrigeration system.  The worst case scenario considered the loss of the total charge of 11,000  pounds of anhydrous ammonia in the refrigeration system over a 10 minute period.  The analysis showed that the ammonia vapor could travel approximately  3,168 yards or 1.8 miles.  There are approximately  13,745 residents which could be potentially affected in the identified radius.  There are other public receptors (hospitals, schools, recreational areas and industrial/commercial buildings) in the potentially affected area. 
 
   The alternative release scenario 
, which is the most likely scenario, considered a release of ammonia from a broken line outside the building.  A release of 2176 pounds of ammonia over a 10 minute period was considered.  The computer model showed that the ammonia vapor could travel approximately 320 yards or 960 feet.  There are approximately 1000 residents and other public receptors (industrial/commercial buildings) located in the potentially affected area.  No administrative controls or mitigation measures were used to limit the chemical release distances for either scenario.  A full copy of the offsite consequence analysis is included in Appendix A. 
 
   The COS Samoa Packing Company has an established Emergency Action Plan to respond to emergencies.  The plan was developed in accordance with 29 CFR 1910.38 Emergency Action Plan.  The plan requires employees to exit the facility during a fire or ammonia release to a safe area.  The emergency agencies will be notified of the emergency.  The emergency agencies will noti 
fy any potentially affected neighbors.  Maintenance personnel will be available as a resource during an ammonia release emergency.  The plan also addresses natural hazard emergencies, fires, bomb threats, civil disturbances, and utility outages. 
 
   This location has not experienced a reportable ammonia release in the past 5 years. 
        
   The COS Samoa Packing Company wanted to evaluate the potential failures of the refrigeration system, and if the safeguards were sufficient to prevent a catastrophic release of ammonia.  A Process Hazard Analysis was completed on the refrigeration system in January, 1995.  Planned changes to improve safety resulting from this analysis are documented in the Process Hazard Analysis report in the Accidental Chemical Release Prevention Program.  Also, the guidelines from the International Institute of Ammonia Refrigeration (IIAR) will be followed where applicable, to manage the refrigeration system.
Click to return to beginning