McLane Distribution SunEast - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

MCLANE DISTRIBUTION - SUNEAST 
RISK MANAGMENT PLAN  
 
Executive Summary 
 
 
1.  ACCIDENTAL RELEASE PREVENTION AND EMERGENCY RESPONSE POLICIES. 
 
At this McLane Distribution facility, we utilize anhydrous ammonia which is considered hazardous by the Environmental Protection Agency (EPA).  The properties which make ammonia valuable as a refrigerant also necessitate certain safety precautions.  McLane strives to protect all its valuable resources and assets - both personnel and property.  We live and have families in this community.  We want to prevent exposure to all our personnel as well as nearby members of our community, existing natural resources, and the surrounding environment.  It is our policy to comply with all Federal, State, and Local regulations.  Through continual, accurate training and various safety devices and procedures, we work to minimize potential releases. 
 
Our emergency response program has specific procedures for accidental releases of anhydrous ammonia as well as other 
emergencies.  We work in conjunction with the Kissimmee Fire Department and the Local Emergency Planning Committee to prepare for necessary notification of all affected neighbors. 
 
 
2.  THE STATIONARY SOURCE AND REGULATED SUBSTANCES HANDLED. 
 
The primary purpose of our facility is the temporary storage of refrigerated and frozen foods.  We utilize anhydrous ammonia as the primary means for refrigeration and freezing.  An outside company is used to fill our main receiver tanks.  Piping then carries the ammonia to the needed refrigeration or freezing units.  Access to the site is restricted to facility employees, authorized management personnel and authorized contractors. 
 
The regulated substance used at our facility is anhydrous ammonia.  The maximum amount of ammonia stored at this facility is 12,900 pounds.  We have this capacity but generally run up to 80% of total capacity. 
 
 
3.  THE WORST CASE RELEASE SCENARIO(S) AND THE ALTERNATIVE RELEASE SCENARIO(S), INCLUDING ADMINISTRATIVE CO 
NTROLS AND MITIGATION MEASURES TO LIMIT THE DISTANCES FOR EACH REPORTED SCENARIO. 
 
Worst Case Scenario 
The worst case scenario would be failure of our largest receiver.  The capacity of this tank is 7,555 pounds.  It is assumed that the entire contents are released as a two phase flow (gas and aerosol-ALOHA). 
Distance to endpoint: 0.91 miles (1,597 yards) 
 
Alternative Scenario 
The alternative scenario would be the release of ammonia due to the failure of a pressure release valve.  The emergency valves shut-down release would engage and stop the flow and sounds an alarm.  The monitoring system would alert personnel to manually shut the valve.  The maximum time of the release would be 31 minutes and maximum quantity released would be approximately 1,165 pounds of ammonia.   
Distance to endpoint:  0.10 miles (180 yards) 
 
 
4.  FIVE-YEAR ACCIDENT HISTORY. 
 
To date, this McLane DC facility has not incurred a reportable release. 
 
 
5.  THE RMP MANAGEMENT PROGRAM. 
 
The management of the RMP pro 
gram will be handled by Mr. Jimmie Clark  Mr. Clark will administrate in conjunction with the McLane Distribution management and personnel.  Other entities or organizations that will be coordinated with include the Kissimmee Fire Department and HAZMAT team. 
 
 
6.  THE GENERAL ACCIDENTAL RELEASE PREVENTION PROGRAM AND THE SPECIFIC PREVENTION STEPS. 
 
The McLane DC facility complies with all applicable Federal, State and Local regulations including the EPAs Accidental Release Prevention Rule.  Our personnel are trained about this during our Hazard Communications Training and through access to our Written Programs.  Our Refrigeration Maintenance operators receive a combination of classroom plus On-The-Job training(OJT).  They are given written tests and are observed by senior maintenance in order to demonstrate proper job skills and knowledge.  Also, the ammonia system is operated, tested and maintained to the standard of International Institute of Ammonia Refrigeration, the most stringent 
standards of the industry. 
 
 
7.  THE EMERGENCY RESPONSE PROGRAM. 
 
We work very closely with the Osceola Public Safety Chief and the Kissimmee Fire Department and HAZMAT team on emergency preparedness.  We meet periodically with representatives of each to address any changes in the facility or any new concerns. 
 
Also, we have onsite Hazardous Materials trained personnel to immediately respond to adverse conditions.  This helps minimize the potential of an offsite release. 
 
 
8.  PLANNED CHANGES TO IMPROVE SAFETY. 
 
Currently, McLane Distribution trains and tests all refrigeration technicians.  Our preventative maintenance program is above standard and our ammonia Process Safety Program is reviewed and updated annually.  Our program is improved continuously through annual updates of our written program and annual training of our technicians.  We also take advantage of new technologies when safer and more economical alternatives are available.