SSE MFG., INC. -TINO'S - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

Schwan's has historically placed a high priority on chemical 
safety. The corporate environmental compliance manager has been  
assigned overall responsibility for chemical safety in general and  
for ammonia refrigeration safety in particular since 1991.  
Schwan's maintains 3 - shift coverage of emergency responders  
trained to the 24-hour technician level at all facilities with  
ammonia refrigeration systems covered by this rule. 
 
The Norwood Young America, MN facility manufactures frozen food  
products. Anhydrous ammonia is used in the refrigeration system at  
this facility. Ammonia is the most efficient and environmentally  
compatible refrigerant available. Although it is toxic at high  
concentration and is an irritating gas, it is not a cumulative  
metabolic poison, does not cause cancer or other dread diseases  
and does not cause lasting environmental damage. The refrigeration  
system at this facility contains about 27,300 pounds of ammonia.  
The refrigeration system was installed i 
n 1994 and is a nearly  
new state of the art, system. 
 
Schwan's calculates ammonia worst case release scenarios using the  
Model RMP for Ammonia Refrigeration, May 1996. All Schwan's  
manufacturing facilities are located in areas that meet the  
definition of "urban". Schwan's has chosen to calculate worst case  
release poundage for the largest high-pressure receiver in the  
system, filled to full calculated hydraulic capacity. Reduced  
volume for administrative controls was not used, since the  
described scenario would probably occur only as a result of a  
catastrophic vessel rupture caused by a total filling of the  
vessel, closure of all vessel block valves, failure of all  
pressure relief valves, with a simultaneous increase in liquid  
temperature sufficient to overpressure the vessel to the point of  
failure. 
 
It is the professional judgement of Schwans Environmental Health  
and Safety Department that a release rate of 400 lb./min. should  
be used as an alternate case scenario in  
lieu of the 100 lb./min.  
rate suggested in the Model RMP. 
 
The "urban" site condition will be used. 
 
Based on the above, the worst-case ammonia release scenario for  
the Norwood Young America, MN facility will be 26,000 pounds  
released over a 10-minute period. The alternate case will be a  
release rate of 400 pounds per minute. Both scenarios have off- 
site impacts. 
 
The ammonia refrigeration system is covered by the OSHA Process  
Safety Management (PSM) rule, 29 CFR 1910.119. 
 
The Norwood Young America, MN facility maintains a 3-shift  
emergency response team, trained at the 24-hour technician level.  
The team numbers 8 members. The training is conducted by the  
Corporate Environmental Compliance Manager. The training is  
designed with a heavy emphasis on ammonia safety, mechanical  
isolation, personal protective equipment up to use of Level `A'  
suits and interaction with an incident command system (ICS).  
Copies of emergency plans are filed with the Fire Department and  
annual fac 
ility walkthroughs are conducted with Fire Officers.  
Preplanned command posts and staging areas have been designated  
and Incident Command transfer and liaison functions have been  
established. A post-incident debriefing will be conducted after  
each incident. 
 
Since a continuous improvement philosophy is deeply imbedded in  
the Schwan's corporate culture, improvements in system safety are  
implemented as a result of employee-based involvement, a  
designated PSM team and as a result of system engineering  
modifications and extensions. Post incident debriefings and  
incident investigations will be used to identify additional  
improvements to system safety.
Click to return to beginning