Northeast Wastewater Treatment Facility - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

Executive Summary 
 
 
 
Accidental Release and Emergency Response Policies 
 
The City of Lincoln Northeast WWTF has operated their disinfection, dechlorination, and propane processes without incident for the past five years.  This successful operating record is due to the City's commitment to ongoing training programs, operating procedures, and computer-generated maintenance activities. 
 
Stationary Source and the Substance Handled 
 
The City of Lincoln operates an 8-MGD (by design) municipal wastewater treatment facility at 7000 North 70th Street.  Discharge from the treatment facility enters Salt Creek.  The facility uses chlorine to reduce the pathogenic (disease causing) bacteria and viruses in the wastewater discharge to levels below those which can be achieved through ordinary secondary treatment.  The use of chlorine reduces the threat to the quality of recreational waters.  
 
The facility uses sulfur dioxide to remove residual chlorine remaining after the disinfection process and prio 
r to  discharging to the receiving waters.  This is done because it has been shown that residual chlorine is harmful to some species of fish and carcinogenic to other wildlife. 
 
Chlorine and sulfur dioxide utilized in the disinfection and dechlorination processes arrive at the facility in one ton containers that are stored inside a ventilated building equipped with leak detection devices.  The maximum quantities of chorine and sulfur dioxide stored at the facility are 16,000 pounds and 8,000 pounds, respectively.   
 
The facility uses propane for building heat and as a supplemental source of digester heat.  Propane is stored in four 1,000-gallon tanks and one 18,000-gallon tank.  The maximum quantity of propane stored at the facility is 76,000 pounds.  
 
Off-Site Consequence Analysis 
 
One worst-case release scenario and one alternative release scenario was assessed for the chlorine, sulfur dioxide, and propane processes.  To ensure a common basis for comparisons, EPA defined the worst-ca 
se scenario as the release of the largest quantity of a regulated substance from a single vessel or process line that results in the greatest distance to an endpoint.  The worst-case scenario allows consideration of passive mitigation measures.  The worst-case release scenarios for the chlorine, sulfur dioxide, and propane processes were determined in accordance with the requirements provided in 40 CFR 68.22 and 40 CFR 68.25(b,c). 
 
The alternative release rate is a release that is considered more reasonable or "more likely."  The alternative release scenarios for the chlorine, sulfur dioxide, and propane processes were determined in accordance with the guidelines in 40 CFR 68.22 and 68.28.  Active mitigation measures, as well as passive mitigation measures, can be used in determining the alternative release scenario. 
 
According to EPA, the toxic endpoint for chlorine and sulfur dioxide have been defined to be 0.0087 mg/L (3 ppm) and 0.0078 mg/L (3 ppm), respectively.  An airborne conce 
ntration that is used as the toxic endpoint is the maximum airborne concentrations below which it is believed that nearly all individuals can be exposed for up to one hour without experiencing or developing irreversible or other serious health effects. 
 
According to EPA, the explosion endpoint for propane has been defined as the distance at which there is an overpressure of 1 psi.  This explosion endpoint is the farthest distance of release at which the explosion causes the pressure on a person or building to exceed atmospheric pressure by 1 psi. 
 
The distance to the toxic or explosion endpoint becomes a radius for a circle around the covered process.  Residential population within the circle is required to be determined based on available census information.  The population number is reported as part of the EPA submittal.  This method greatly overestimates the population potentially exposed to a chlorine or sulfur dioxide release, because the chlorine or sulfur dioxide plume would see 
k lowest elevations in the direction of the prominent winds.  Since wind direction cannot be anticipated for an accidental release, EPA mandated the circle estimation method. 
 
Release scenarios and distances to toxic or explosion endpoints are discussed in more detail in the subsequent paragraphs. 
 
Chlorine 
 
Worst-Case Release Scenario 
 
For the chlorine process at the Northeast WWTF, the worst-case release results from a one-ton chlorine cylinder (maximum amount held in a single vessel) rupturing when unloaded from the delivery truck and its contents escaping to the atmosphere in 10 minutes.  In the event the cylinder would release its entire contents to the atmosphere in 10 minutes, the release rate would be 200 pounds per minute.  The distance to the toxic endpoint worst-case release distance, 1.3 miles, was taken from Exhibit 4-3 of the EPA's Risk Management Program Guidance for Wastewater Treatment Plants, for an urban setting. 
 
The residential population within the 1.3-mile radius 
of influence was determined to be approximately 350 people.  The population was calculated by utilizing the U.S. Department of Commerce software package LandViewTM III, which sums 1990 population information from the Census Bureau for areas within the 1.3-mile radius impact zone.  
 
Alternative Release Scenario 
 
The alternative release scenario, or scenario more likely to result in a release, involves a chlorine storage cylinder and other equipment such as ladders or tools dropping on or hitting the flexible connector.  The flexible connector ruptures, releasing 2 pounds of chlorine gas for 20 minutes.  This results in a release rate of 0.1 pounds per minute.  The distance to the toxic endpoint alternative release distance, 0.10 miles was taken from Exhibit 4-15 of the EPA's Risk Management Program Guidance for Wastewater Treatment Plants, for an urban setting. 
 
The residential population within the 0.10-mile radius of influence was determined to be 0 people.  The population was calcul 
ated by utilizing the U.S. Department of Commerce software package LandViewTM III, which sums 1990 population information from the Census Bureau for areas within the 0.10-mile radius impact zone.  
 
Sulfur Dioxide 
 
Worst-Case Release Scenario 
 
For the sulfur dioxide process at the Northeast WWTF, the worst-case release results from a one-ton sulfur dioxide cylinder (maximum amount held in a single vessel) rupturing when unloaded from the delivery truck and its contents escaping to the atmosphere in 10 minutes.  In the event the cylinder would release its entire contents to the atmosphere in 10 minutes, the release rate would be 200 pounds per minute.  The distance to the toxic endpoint worst-case release distance, 1.3 miles, was taken from Exhibit 4-5 of the EPA's Risk Management Program Guidance for Wastewater Treatment Plants, for an urban setting. 
 
The residential population within the 1.3-mile radius of influence was determined to be approximately 350 people.  The population was cal 
culated by utilizing the U.S. Department of Commerce software package LandViewTM III, which sums 1990 population information from the Census Bureau for areas within the 1.3-mile radius impact zone.  
 
Alternative Release Scenario 
 
The alternative release scenario, or scenario more likely to result in a release, involves a sulfur dioxide storage cylinder and other equipment such as ladders or tools dropping on or hitting the flexible connector. The flexible connector ruptures, releasing 2 pounds of sulfur dioxide for 20 minutes.  This results in a release rate of 0.1 pounds per minute.  The distance to the toxic endpoint alternative release distance, 0.10 miles was taken from Exhibit 4-17 of the EPA's Risk Management Program Guidance for Wastewater Treatment Plants, for an urban setting. 
 
The residential population within the 0.10-mile radius of influence was determined to be 0 people.  The population was calculated by utilizing the U.S. Department of Commerce software package LandViewTM 
III, which sums 1990 population information from the Census Bureau for areas within the 0.10-mile radius impact zone.  
 
Propane 
 
Worst-Case Release Scenario 
 
For the propane process at the Northeast WWTF, the worst-case release involves a release of the entire contents of the largest propane tank.  The capacity of the facility's only tank is 18,000 gallons, which is approximately 76,000 pounds of propane.  The distance to the explosion endpoint worst-case release distance, 0.34 miles, was calculated utilizing the equation from page 4-19 of the EPA's Risk Management Program Guidance for Wastewater Treatment Plants. 
 
The residential population within the 0.34-mile radius of influence was determined to be approximately 40 people.  The population was calculated by utilizing the U.S. Department of Commerce software package LandViewTM III, which sums 1990 population information from the Census Bureau for areas within the 0.34-mile radius impact zone.  
 
Alternative Release Scenario 
 
The alte 
rnative release scenario, or scenario more likely to result in a release, involves damage to the fill station by a moving vehicle or pull away before disconnecting from fill and vapor return lines.  Active mitigation devices(i.e., check valves) would limit the release to only the liquid propane contained in the hose, the quantity released is 69 pounds.  The distance to the explosion endpoint alternative release distance, 0.03 miles, was calculated utilizing the equation from page 4-19 of the EPA's Risk Management Program Guidance for Wastewater Treatment Plants. 
 
The residential population within the 0.03-mile radius of influence was determined to be 0 people.  The population was calculated by utilizing the U.S. Department of Commerce software package LandViewTM III, which sums 1990 population information from the Census Bureau for areas within the 0.03-mile radius impact zone.  
 
Accidental Release Prevention Program 
 
The City of Lincoln has developed a Prevention Program in accordance 
with the requirements of 40 CFR 68 for Program Level 2.  The City will continuously evaluate and update their safety and prevention procedures as needed.  The City conducted a process hazard review for the processes determined to be "covered", the chlorine, sulfur dioxide, and propane processes, as part of the development of the Risk Management Program Plan. 
 
Five-Year Accident History 
 
No accidents, as described under 40 CFR 68.42(a), have occurred at the Northeast WWTF in the previous five years. 
 
Emergency Response Program 
 
The emergency response program established by the City of Lincoln for the Northeast WWTF does not require personnel to respond to accidental releases of regulated substances.  The local emergency response agencies will be relied upon for coordinating all response actions resulting from the release and for informing the public about the release.  The facility has developed an Emergency Action Plan outlining actions taken in the event of an accidental release of r 
egulated substances as well as in the event of natural disasters. 
 
Safety Improvements 
 
The facility is currently in the process of evaluating the recommendations from the process hazard review completed in February 1999.  Any improvements made in response to the recommendations will be documented.
Click to return to beginning