Iowa Double Circle Libertyville - Executive Summary

| Accident History | Chemicals | Emergency Response | Registration | Source | Executive Summary |

Risk Management Plan - Executive Summary 
 
Facility:      Iowa Double Circle,  Libertyville,IA 
Contact:     Fred Filson 
Phone:       800-447-4148 
 
1.  Facility Policy. 
 
    The owners, management and employees of Iowa Double Circle (Libertyville) are 
    committed to the prevention of any accidental releases of anhydrous ammonia and 
    propane.  If an accidental release should occur, the facility is prepared to work with the 
    local fire department, or other authorities, to mitigate and minimize the impacts of the 
    release to the people and the environment. 
 
2.  Facility Information. 
 
    The primary activity at the facility is the storage and blending of fertilizers for the sale to 
    farmers.  Anhydrous ammonia is received, stored and distributed for both direct 
    application and for blending into mixed-grade fertilizers for crop production nutrients. 
    The maximum quantity stored would be 238,000 pounds of ammonia and 113,200 
    pounds of propane. 
 
3.  Worst-Cas 
e Scenario and Alternate Release Scenario. 
 
    a.     The worst-case scenario would be the release of the total contents of a storage 
             tank released as gas over a period of 10 minutes. 
 
            Anhydrous Ammonia - The maximum quanity released would be 127,500 pounds, 
            which represents the volume of the largest storage tank at 85 percent capacity as 
            limited by design standards.  The distance to the end point (point of dispersion to 
            200 parts per million, or ppm) is 2.6 miles. 
 
            Propane - The maximum quantity released would be 56,000 pounds.  The distance 
            to the end point (point of 1 psi overpressure) is 0.3 miles. 
 
    b.     The alternate release scenario, based on the five-year accident hjistory ( or the most 
            likely potential incident), is as follows: 
 
            Anhydrous Ammonia - The alternate release scenario is a release from a break in a 
            3 - inch transfer hose followed 
by release of ammonia for 2 minutes before an 
            automatic or manual shut-off intervenes and stops the flow of ammonia.  The 
            maximum quantity released would be 69 pounds.  The distance to the endpoint 
            (point of dispersion to 200 ppm) is 0.03 miles. 
 
4.  Accidental Release Prevention Program.      
 
    The facility has been reviewed for general compliance with the provisions of "Safety 
    Requirements for the Storage and Handling of Anhydrous Ammonia, K-61.1", published 
    by The American National Standards Institute, Inc. (ANSI), and the standards of the U.S. 
    Occupational Safety and Health Administration (OSHA), 29 CFR 1910.111, "Storage and 
    Handling of anhydrous ammonia".  The ANSI Standard has been adopted by reference by 
    Iowa Administrative Code Part 21 - Chapter 43 - Rule 43.6(200) - Standard for the storage 
    and handling of anhydrous ammonia.  The applicable standard for propane is NFPA - 58. 
    The OSHA standard is 
referenced in the Registration Form Section 8.3.b. 
 
5.   Five-Year Accident History. 
 
    There have been no accidental releases of anhydrous ammonia or propane in the past five 
    years that:  have caused any deaths, injuries or significant property damage at the facility; 
    nor to our knowledge, have resulted in off-site deaths, injuries, evacuations, sheltering in 
    place, property damage, or environmental damage. 
 
6.  Emergency Response Program. 
 
    The facility has: 
 
    a.     a written action plan, in accordance with OSHA standard 29 CFR 1910.38; 
 
    b.     provided state and local authorities with the emergency planning and community 
            right-to-know information as required under SARA Title III (EPCRA). 
 
7.  Planned Changes to Improve Safety. 
 
    Safety improvement is an on-going process at the facility.  Periodic evaluations are 
    performed to assess the maintenance of safe conditions.  There are no additional specific 
    safety recommendations  
regarding storage or use of anhydrous ammonia and propane for 
    implementation at this time.
Click to return to beginning